• Vb85 33kv/1250A-25ka Indoor Frontal Drawable Embeded Pole Vacuum Circuit Breaker
  • Vb85 33kv/1250A-25ka Indoor Frontal Drawable Embeded Pole Vacuum Circuit Breaker

Vb85 33kv/1250A-25ka Indoor Frontal Drawable Embeded Pole Vacuum Circuit Breaker

Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Vacuum
Installation: Insert
Structure: Vcb
Samples:
US$ 1000/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
VB85
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
VDE, ISO9001-2000, Type Tested
Transport Package
Wooden Case
Trademark
FARADY
Origin
Zhejiang, China
HS Code
85372090
Production Capacity
20000

Product Description

Overview

 
VB85 33 indoor high voltage vacuum circuit breaker is a new developed product JiaJi electric co., LTD., mainly for the rated voltage 40.5 kV, three-phase ac 50 hz, power system for industrial and mining enterprises, power plants and transformer substation protection and control, especially suitable for frequent operation. Conformity with GB11022 "high voltage switch equipment and control equipment standards of common technical requirements, GB1984 ac high voltage circuit breaker and IEC56 high voltage circuit breaker and other standards.

 

Service Condition

Ambient temperature: not higher than +40 °C, not less than -10°C (at -30 °C to allow storage and transportation).
Altitude: not exceed 1000m.
Relative humidity: daily average of not more than 95%,saturated vapor pressure on the average of not more than 2.2 × 10-3MPa, On average not more than 1.8 × 10-3MPa.
Earthquake intensity: not more than eight.
No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.

 

Technical Parameters

Item Description Unit Data
1 Rated voltage KV 40.5
2 Max. voltage KV 40.5
3 Rated current A 1250/1600/2000/2500/3150
4 Rated break current on shorting KA 31.5/40/50
5 Rated short circuit making current KA 80/100/125
6 Rated peak withstand current KA 80/100/125
7 4S Rated withstand current KA 31.5/40/50
8 Rated insulation level Power frequency voltage(when losing a circuit) KV Dreaker 48
Impulse withstand voltage(when losing a circuit) Dreaker 84
9 Rated operating sequence   OC-0.3s-CO-180S-CO
10 Mechanical life Times 10000
11 Open circuit times of rated short dropout current Times 50
12 Rated close brake voltage of operating machnie V 110,220
13 Rated break brake voltage of operating machnie V 110,220
14 Clearance between open contacts mm 11±1
15 Exceed range(the compress length of contact sping) mm 4±0.5
16 Different period of three-phase break and close break ms ≤2
17 The jump time of contact close break ms ≤2
18 Average break speed m/s 0.9~1.2
19 Average closing speed m/s 0.6~1.2
20 Opening time Ubder max.operating voltage S ≤0.05
Under min.operating voltage ≤0.08
21 Closing time s ≤0.1
22 Resistance of each phase main loop μΩ ≤40
23 Contacts limit ersion mm 3

 

Vb85 33kv/1250A-25ka Indoor Frontal Drawable Embeded Pole Vacuum Circuit Breaker

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory
Registered Capital
7.67 Million USD
Plant Area
3775 square meters