Basic Info.

Model NO.
LW3F
Product Name
Outdoor Pole-Install Load Switch/Sectionalizer
Function
Over Voltage Protection, Overcurrent Protection
Certificcation
Type Tested
Material
Stainless Steel
Transport Package
Wooden Case
Trademark
farady
Origin
Zhejiang, China
HS Code
8535900090
Production Capacity
20000pieces/Year

Product Description

General

LW3F type pole-install load switch was used in 12kV,24kV,33kV rated voltage, rated current 400/630A; 50/60HZ with the load current; over load current of power line open circuit and opening and closing electric systems.The switch can equiped with a conttoller with most advanced technical parameter.

LW3F-A type LW3F is manaully LBS for choice.
LW3F-M type LW3F is a intelligent type LBS for choice. It can automatically disconnect when the distribution line was break down. It could operated by handle; Implementt electro motion and distant. The electric controller was installed in stainless steel cabinet. So it could use in any conditions.

Service environment

1.Air temperature:Maximum temperature: +40ºC; Minimum temperature:-20ºC
2.Humidity:Monthly average humidity 95%; Daily average humidity 90% .
3.Altitude above sea level:Maximum installation altitude: 2500m.
4.Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
5.No frequent violent shake
Technical data
No
Item

Unit

Data

1

Rated voltage

kV

12/20/33

2

Rated current

Hz

50/60


3

Rated insulation level

(with SF6 gas 0.07Mpa)

lightning impulse voltage

kV

75/125/170

Power frequency impulse voltage

kV

42/50/70

5

Rated current

A

630

6
Rated open circuit load current(0.07Mpa//20ºC/h)
A

630

7

Open circuit current under 0 pressure

A

630

8

Rate peak value withstand current

kA

50

9

Rated short-time closing current

kA

50

10

Rated short-time withstand current

kA/s

20/1

11

Rated electric cable charge open circuit current

A

25

12

Rated wire charge open circuit current

A

16

13

Rated closed loop open circuit current

A

630

14

Excitation current

A

21

15

Rated current open circuit times

≥400 times

16

Rated working pressure

MPa

0.07

17

Each operating voltage and resistance

μΩ

≤150

18

Gas relative leakage rate

year

≤1%


19

SF6 gas moisture content

Leave factory relative figure

ppm

≤150

Switch working figure

ppm

≤300

20

Machine stable operation

times

6000


21


Rated operating voltage and assistant loop rated voltage

V

DC220;110

AC 220;110


22

Weight

M type

kg

115

A type

135
Certification
24kv/630A Outdoor Pole-Install Load Switch/Sectionalizer
Packing & Delivery
24kv/630A Outdoor Pole-Install Load Switch/Sectionalizer
About us
24kv/630A Outdoor Pole-Install Load Switch/Sectionalizer

Zhejiang Farady Powertech Co.,Ltd
 
 
Http:// faradypowertech.en.made-in-china.com
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier