Flbs36-24kv/1250A-16ka Indoor Manully Operation Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs)

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Still deciding? Get samples of US$ 500/Piece
Request Sample

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
7.67 Million USD
Plant Area
3775 square meters
  • Flbs36-24kv/1250A-16ka Indoor Manully Operation Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs)
  • Flbs36-24kv/1250A-16ka Indoor Manully Operation Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs)
Find Similar Products

Basic Info.

Model NO.
FGB1
Arc-extinguishing Medium
SF6
Installation
Fixed
Structure
Load Break Switch
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
VDE, ISO9001-2000, Load Break Switch
Transport Package
Wooden Case
Trademark
FARADY
Origin
Zhejiang, China
HS Code
85372100
Production Capacity
50000

Product Description

++++General
FLBS an indoor high-voltage SF6 load switch, an switchgear with the rated voltage of 12kV/24kV, adopted with SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off and to-ground, and is characteristic in its small volume, its convenient installation and operation and its the great adaptability with surroundings.
FLBS of an indoor high-voltage SF6 load switch and FLBS of SF6 load switch plus fuse combination can function to protect and control the electric equipments for power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation.
FLBS of an indoor high-voltage SF6 load switch and FLBS load switch plus fuse combination are complied with the standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc..

++++Service environment
a) Air temperature
Maximum temperature: +40ºC; Minimum temperature:-35ºC
b) Humidity
Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level
Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake

++++ Main technical specifications

No Item Unit Parameter
1 Rated voltage kV 12 24
2 Rated frequency Hz 50/60
3 Rated current A 630/800
4 1min Power frequency
withstand voltage
wet kV 38 50
dry kV 48 60
5 Lightning impulse withstand voltage kV 75 125/150
6 Rated short circuit breaking current (peak) kA 80 63
7 Rated active load and close circuit breaking current A 63 50
8 Rated transferring current A 1700 1200
9 Rated short circuit making current (peak) kA 80 63
10 Rated cable(line) charging breaking current A 50 and 10
11 Cable charge breaking current in earthing fault A 20 20
12 Rated withstand current (peak) kA 80 63
13 Short time withstand current (2s) kA 31.5 25
14 Mechanism life times 5000 2000

Note: For short circuit breaking and peak current is based on Fuse plus combination. 
++++Installation, Maintenance & Service.

++++Installation, Adjustment

FLBS type load break switch has been strictly tested before outgoing from the factory, and fully meet the technical standards, must carefully read the installation manual and prepare as below before the installation and adjustment.
Check the external appearance, any damage product is not allowed to use.
Clean the equipment and get rid of the dust and dirt may cause by the transportation or other causes.
After installation, be sure the load break switch is turned off, insert the handle to the earthing operating hole in the up part of operating panel, and rotate the handle clockwise in 180o to earth the switch, rotate counterclockwise in 180o to switch off the earth.
For switching on, turns off the load break switch firstly, insert the handle to the load break switch operating hole in the lower part of panel and turn on the load switch.
From the switch on to switch off, for K type mechanism, insert the handle to the load switch operating hole and rotate it in 180o to switch off; for A type mechanism, press the "switch off" button to switch off the load break switch, observe from the winder to confirm it, check whether the on/off indication plate works properly.
Notice: only when the load break turns off, can turning on and earthing operation be done !

++++Maintenance & Service
On condition of installing in environment as this manual required and normal operations, product guaranteed to be fault free for 10 years and has a running life of 25 years, but regular check per 6 months is required.

Keep the external appearance away from dust, dirt and damp.
Lubricate and operate the mechanism for 3-5 times, check whether it acts properly.
Check with the pressure meter regularly, in case of meter data lower than 0.01MPa, should reload gas.
When the malfunction happens in the load break switch and fuse combination, and one of the three phase immediately, gas charging should be done by professional personnel from or trained by the manufacturer. uses burns out, all three fuses should be replaced at one time, must earth the switch before the replacement.

++++Matters need attention
It is NOT allowed to disassembly the self-sealed valve in front of switch( connecting end of meter).
It is NOT allowed to unload the seal screws on switch at any time.

+++Packaging & Shipping +
Flbs36-24kv/1250A-16ka Indoor Manully Operation Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs)

++++About Us
Founded in 1996, with a registered capital of 10 million USD, Zhejiang Farady Electric enjoys about 20 years' experience in MV transmission and distribution electrical equipment manufacture.
We are National Hi-tech enterprise, National Spark plan Program, State Hi-tech enterprise, State Innovation R&D center, Patent demonstrate company.

Farady is located in Liushi of Yueqing, Zhejiang, China, main products include: Transformer/RMU/switchgear/AVR/ACR and MV indoor and outdoor switch. All the products of ours have passed the national and international laboratory type test, Farady Electric was qualified supplier of China State Grid and China southern Grid.
With ISO9001/14001/18001, we are strike for create value for our partner and customer.
There is more than 20 distributors and agents worldwide already trust us and distribute Farady product there, we are not only export product, but also provide whole technology solution to help partner to establish local factory in our business line.
Today, boasting the value of products specialization, brand management, and business globalization, with the sprits of pragmatism, innovation, efficiency, and responsibility, Farady Company is dedicated to become the top name in the international business from china, and contributes its share to the transformation from the Made in China into the Invented in China.





Copyright 2014 Farady Electric 
Zhejiang Farady Powertech Co.,Ltd
TEL:0086-0577-61512688
Fax:0086-0577-61510628
Http:// faradypowertech.en.made-in-china.com
 
Add: N.O.278,Wei 7 Rd,Yueqing Economic development Zone,Liushi,Yueqing,Zhejiang,P.R.China, 325600

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier