Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 1000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SI. NO. | Item | Unit | Data | Remark |
1 | Rated voltage | kV | 24 | |
2 | Rated frequency | Hz | 50 | |
3 | Rated current | A | 630 | |
4 | Rated short-circuit breaking current | kA | 20 | |
5 | Rated peak withstand current (peak) | kA | 50 | |
6 | Rated short-time withstand current/duration | kA/s | 20/4 | |
7 | Rated short-circuit closing current (peak) | kA | 50 | |
8 | Rated operation sequence | Break-0.3S-close, break-180S- close, break | ||
9 | Mechanical life | Times | 10000 | |
2000 | Disconnector | |||
10 | Rated current breaking times | Times | 10000 | |
11 | Rated short-circuit current breaking times | Times | 30 | |
12 | Main circuit 1min power frequency withstand voltage (inter-phase, to earth, opening) |
kV | 42/48 | Wet 34 |
13 | Lightning impulse withstand voltage (inter-phase, to earth, opening) |
kV | 75/85 | |
14 | Secondary circuit 1min power frequency withstand voltage | kV | 2 |