Sf6 Load Breaker Switch in Ring Main Unit Farady

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Still deciding? Get samples of US$ 1000/Piece
Request Sample

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
7.67 Million USD
Plant Area
3775 square meters
  • Sf6 Load Breaker Switch in Ring Main Unit Farady
  • Sf6 Load Breaker Switch in Ring Main Unit Farady
  • Sf6 Load Breaker Switch in Ring Main Unit Farady
  • Sf6 Load Breaker Switch in Ring Main Unit Farady
Find Similar Products

Basic Info.

Model NO.
FLN36
Speed
High-Speed Circuit Breaker
Arc-extinguishing Medium
SF6
Installation
Insert
Structure
ACB
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker
Certification
ISO9001-2000
Transport Package
Wooden Case
Trademark
Farady
Origin
Zhejiang
HS Code
8536500000
Production Capacity
2000pecies/Year

Product Description

++++General
FLBS an indoor high-voltage SF6 load switch, an switchgear with the rated voltage of 12kV/24kV, adopted with SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off and to-ground, and is characteristic in its small volume, its convenient installation and operation and its the great adaptability with surroundings. FLBS of an indoor high-voltage SF6 load switch and FLBS of SF6 load switch plus fuse combination can function to protect and control the electric equipments for power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation.
FLBS of an indoor high-voltage SF6 load switch and FLBS load switch plus fuse combination are complied with the standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc..
++++Service environment
  1. Air temperature
Maximum temperature: +40ºC; Minimum temperature:-35ºC
  1. Humidity
Monthly average humidity 95%; Daily average humidity 90% .
  1. Altitude above sea level
Maximum installation altitude: 2500m
  1. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
  2. No frequent violent shake
++++ Main technical specifications
No Item Unit Parameter
1 Rated voltage kV 12 24
2 Rated frequency Hz 50/60
3 Rated current A 630/800
4 1min Power frequency withstand voltage wet kV 38 50
dry kV 48 60
5 Lightning impulse withstand voltage kV 75 125/150
6 Rated short circuit breaking current (peak) kA 80 63
7 Rated active load and close circuit breaking current A 63 50
8 Rated transferring current A 1700 1200
9 Rated short circuit making current (peak) kA 80 63
10 Rated cable(line) charging breaking current A 50 and 10
11 Cable charge breaking current in earthing fault A 20 20
12 Rated withstand current (peak) kA 80 63
13 Short time withstand current (2s) kA 31.5 25
14 Mechanism life times 5000 2000
Note: For short circuit breaking and peak current is based on Fuse plus combination.
 