Customization: | Available |
---|---|
Type: | Distribution Metering Box |
Structure: | Protection |
Still deciding? Get samples of US$ 1000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
C - Cable switch module | F - Cable switch module | V - Cable switch module |
D - Direct cable connection module | De - Direct cable connection module with earthing switch | M - Metering module |
No. |
Description |
Requirement |
1 |
Altitude(installed indoors) |
≤1000m |
2 |
Ambient air temperature |
-5ºC ~ +40ºC |
3 |
Monthly average relative humidity |
≤90%(+25ºC) |
4 |
Anti-seismic intensity |
≤8° |
5 |
Maximum daily temperature difference |
< 25ºC |
No. |
Items |
Unit |
Data |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Main bus-bar rated current |
A |
630 |
4 |
Major loop and ground loop rated short-time withstand current/ time |
kA/s |
20/3 |
5 |
Major loop and ground loop rated peak withstand current(peak value) |
kA |
50 |
6 |
Major loop and ground loop rated short-time making current |
kA |
50 |
7 |
Load switch rated current breaking times |
time |
100 |
8 |
Rated transfer current |
A |
1700 |
9 |
Fuse maximum rated current |
A |
125 |
10 |
Fuse breaking current |
kA |
31.5-50 |
11 |
Mechanical endurance |
time |
2000 |
12 |
1min power frequency withstand voltage(effective value) |
kV |
42/48 |
13 |
Lighting impulse withstand voltage inter-phase, to ground, isolation break(peak value) |
kV |
75/85 |
14 |
Secondary loop 1min power frequency withstand voltage |
kV |
2 |
15 |
Protection degree |
|
IP2X |
16 |
External dimension(width * depth * height mm) |
mm |
500(375 750) × 940×1900 800×1200×2200 |
Upper front cover 1. Manometer 2. Nameplate module 3. Short circuit indicator 4. Capacitive voltage indication 5. Load break / earthing switch position indicator 6. Push buttons close/open operation 7. Charged spring indicator 8. Self-powered protection relay 9. Vacuum circuit-breaker position 10. Operation shaft 11. Padlock device Lower front cover 12. Nameplate switchgear 13. Fuse blown indicator 14. Disconnector / earthing switch position indicator 15. Capacitive voltage indication Cable compartment cover 16. Cable compartment cover standard 17. Cable compartment cover with inspection window 18. Support bar (removable) Side cover 19. Lifting lug 20. Operating handle (standard on right hand side) |